NSA, CISA, FBI, DOE, and EPA warn of active AI-assisted attacks against Siemens S7 PLCs across US critical infrastructure sectors. Five U.S. federal agencies issued a joint advisory this week warning of an active hacking campaign against Siemens S7 Series programmable logic controllers. The advisory, CISA AA26-231A, is co-signed by NSA, FBI, DOE, and EPA […]

Five U.S. federal agencies, including the National Security Agency (NSA), Cybersecurity and Infrastructure Security Agency (CISA), Federal Bureau of Investigation (FBI), Department of Energy (DOE), and Environmental Protection Agency (EPA), have issued a joint advisory warning of active, AI-assisted attacks targeting Siemens S7 Series programmable logic controllers (PLCs) across critical infrastructure sectors. The advisory, CISA AA26-231A, confirms that this is an ongoing threat, not a theoretical risk, impacting all S7 generations from the S7-200 to the S7-1500 F-series safety controllers.
Threat actors are reportedly conducting reconnaissance and developing capabilities against U.S.-based Siemens PLC installations. A key aspect of these attacks is the use of AI-generated exploitation scripts, which are disguised as legitimate operational technology (OT) monitoring tools to evade detection. The attackers leverage internet scanning services such as Censys and ZoomEye to identify internet-exposed PLCs running outdated software or those with inadequate security configurations.
The critical infrastructure sectors most affected by this activity include Critical Manufacturing, Energy, Water and Wastewater, Chemical, Food and Agriculture, and Commercial Facilities. The Defense Industrial Base is also specifically named due to its reliance on S7-series hardware.
The attackers are not using custom malware but rather legitimate, open-source industrial automation tools, specifically the `snap7.dll` and `python-snap7` libraries. These libraries facilitate direct communication with Siemens PLCs over the S7comm protocol on TCP port 102, enabling access to PLC memory, configuration data, and ladder logic programs. The use of AI to generate exploitation scripts significantly reduces the technical expertise and time required for adversaries to develop functional ICS exploitation tools, allowing them to rapidly adapt to defensive measures and exploit additional attack vectors.
The observed attack activity unfolds in two distinct phases. Initially, actors use scanning services to locate internet-exposed PLCs. Following this, they perform read operations to understand the target environment, gathering information about specific CPU models and refining their techniques before attempting any write operations. The agencies assess this as a pre-positioning phase, where attackers are mapping environments and testing methods in preparation for potential disruptive actions.
Should these actors escalate from read to write operations, the potential consequences are severe. These include process disruption, equipment damage, and safety incidents through the manipulation of interlocks or emergency shutdown systems, potentially causing cascading effects across interconnected supply chains.
A particular concern highlighted in the advisory is third-party exposure. Asset owners who rely on system integrators or managed service providers for remote PLC access may be unaware that their controllers are internet-accessible. Organizations are urged to verify that connections maintained by external support partners are properly segmented and monitored.
Defenders are advised to monitor for several indicators of compromise. These include S7comm connections originating from devices not typically used for engineering, PLC read or write activity occurring outside of scheduled maintenance windows, and scans of multiple IP addresses on TCP port 102. The presence of Python processes loading `snap7.dll` on systems where it should not be present, along with connections from unexpected countries or locations, should also trigger alerts.
Mitigation strategies prioritize a comprehensive inventory of all controllers, followed by immediate patching, with internet-facing controllers receiving top priority. Organizations should block TCP port 102 at the perimeter firewall, enforce password protection on all controllers, and configure protection levels to restrict unauthorized or low-privilege sessions from reading or writing data. Deploying ICS-aware monitoring solutions capable of baselining legitimate S7comm behavior is also recommended.
Further guidance includes disabling the PLC web server when not needed, limiting simultaneous S7comm sessions, and utilizing TIA Portal's know-how protection and complete restart protection features. The advisory concludes by recommending direct engagement with Siemens ProductCERT for model-specific hardening advice and to verify patch compatibility, a critical step in OT environments where firmware updates can have complex interactions with third-party integrations and may not be easily reversible.
A weakness has been identified in Tenda CP3 27.5.57.101. This issue affects some unknown processing of the file Net/NetCheckPing.cpp. This manipulation of the argument interface_name/host causes os command injection. The attack can be initiated remotely.
A security flaw has been discovered in Tenda CP3 27.5.57.101. This vulnerability affects the function SystemAsh of the file Apis/system.c of the component Kylin. The manipulation of the argument AlarmVoiceURL results in os command injection. It is possible to launch the attack remotely.

OpenAI has announced a $1 billion commitment to provide subsidized access to its Daybreak AI cybersecurity tools for under-resourced critical infrastructure defenders. The initiative, named Daybreak for Frontline Defenders, will offer AI models, training, and technical support over the next six months, prioritizing water and wastewater utilities, electric grid operators, and local government entities. This move aims to equip organizations with limited budgets and staff against increasingly sophisticated cyber threats.

Attackers are exploiting a new unpatched vulnerability in Magento Open Source and Adobe Commerce that lets them run malicious code on an online store's server without logging in, Dutch e-commerce security company Sansec said in an advisory published on September 5. Sansec, which discovered the flaw and named it StyleSmuggler, said attacks started on September 4. "Sansec is publishing early
In BPF instructions that load/store a value from/to a scratch memory register the register index is an unsigned 32-bit integer and must not exceed 15, but libpcap BPF interpreter does not validate the value. In particular uncommon use cases a crafted filter program can cause the interpreter to try reading and writing the OS process memory in the 16GiB starting at the current stack frame on 64-bit architectures and in the entire address space on 32-bit architectures.

Attackers are exploiting two new PaperCut flaws to steal credentials and gain privileged access in education-sector attacks across the U.S. and Europe. Attackers are exploiting two recelty disclosed PaperCut flaws, CVE-2026-81578 and CVE-2026-82078, in attacks targeting schools and other education organizations in the U.S. and Europe, as reported by TheHackerNews. Arctic Wolf researchers observed