The U.S. Cybersecurity and Infrastructure Security Agency (CISA) has issued an industrial control systems advisory regarding a critical vulnerability affecting Danfoss AK-SM 8xxA series refrigeration controllers. The flaw, tracked as CVE-2026-129713, carries a CVSS severity score of 9.8. It stems from a stack-based buffer overflow within an unauthenticated Common Gateway Interface (CGI) handler. By sending specifically crafted HTTP or HTTPS POST requests, a remote attacker could potentially trigger memory corruption, force a web server restart, or execute arbitrary code with the privileges of the web server.
Danfoss officially acknowledged the existence of the vulnerability on November 20, 2026. However, the company confirmed that a software fix is not currently available. A patch is expected to be included in the forthcoming software version 5.5.x. Until that update is released, both Danfoss and CISA have provided interim mitigation guidance for operators of these industrial units.
The recommended security measures include ensuring that devices are not exposed directly to the internet and are not assigned public IP addresses. Operators are advised to restrict remote access to these controllers by utilizing secure VPNs or other protected network architectures. Furthermore, Danfoss has instructed users to configure all affected devices to operate in "Strict mode," a setting that provides enhanced security protections. The manufacturer also noted that it intends to remove the option for customers to disable this mode in the future. Additionally, users are urged to implement strong, unique passwords for all administrative and user accounts.
This advisory follows a series of recent cyberattacks targeting operational technology, including Danfoss refrigeration controllers, which have been linked to Iranian state-aligned actors. Two distinct waves of attacks occurred in October and November 2026. The initial campaign, taking place on October 11 and 12, primarily impacted French supermarket chains, including Intermarché, Coopérative U, Carrefour Market, Monoprix, Leclerc, and Super U. Reports indicated that approximately 700 sites were compromised, with attackers manipulating controllers to increase temperatures, leading to spoiled food and, in some instances, physical fires.
A second wave of attacks occurred on November 1 and 2, utilizing similar tactics and affecting retailers across at least 12 European countries. Beyond the retail sector, these incidents reportedly impacted blood banks in France. While the recent advisory focuses on the AK-SM 8xxA series, these earlier campaigns involved a mix of hardware, including newer models running outdated firmware and older, legacy models such as the AK-SM800 and AK-SC355 that no longer receive security updates. Retailers in the United Kingdom were largely spared from these incidents, as the Danfoss brand maintains a smaller market presence in that region.